Home /8K6 S D-48 ORD2
Vibration | 10 - 55Hz, 19.6m/s² (2G) |
Safety Standards | Design conforms to UL60950-1 |
Mounting | Back plate mounting (Din Rail hole – see page 2) |
Width | 90mm |
Depth | 117mm (without brass terminal) |
Height | 155mm |
Weight (Unpacked) | 3.0 Kg approx. |
Input A Voltage | 48VDC ±10% |
Input B Voltage | 48VDC ±10% |
Input Current | 60A max |
Leakage Current | 200mA max |
Isolation |
Input-Output: Positive Side Input-Case: 2000VAC Output-Case: 500VAC |
Output Voltage | 48VDC ±10% |
Output Current | 60A (2880W) Max (Redundant mode) |
Forward Voltage Drop | 1000mV max on 60A load |
Load Regulation | 800mV max (exclusive of OR-ing diode drop) |
LED Indications | Green LED: Input A, B; Green LED: Output |
Response-up Time | 50ns |
Input Reverse Polarity | Protected |
Efficiency | 95% |
Alarm / PFC Contact |
For Input A & B Fail C, NO close for Input OK C, NO open for Input not OK Rating: 5A @ 230VAC |
Conducted Noise | Depends on input |
Input and Output | M-8 Brass nut & bolt |
PFC | Screw terminal |
Operating Temperature | -20°C to +85°C |
Storage Temperature | -40°C to +100°C |
Relative Humidity | 20-90% RH (Non-condensing) |
Vibration | 19.6 m/s², 10-55 Hz, 3 min period, 60 min each along X, Y & Z axis |
Altitude | 3000m (10,000 feet) max |