Home /IN-R-20K-DF-S-E

| Voltage | 220VDC ± 10%. |
| Current | 120A max. at 220VDC Input |
| Isolation |
Input-GND : 2KV cut off current 40mA. Input-Output : 2KV cut off current 40mA. Output-GND : 500V cut off current 100mA. |
| Transient and surge | Protected. |
| PSU ON / OFF | Provided through MCB. |
| Operating Temperature | -20°C to +70°C |
| Storage Temperature | -20°C to +75°C |
| Relative Humidity | 20-90% RH (Non-Condensing) |
| Cooling | Internal forced cooling from front to rear site. |
| Factory Set Voltage | 110VDC. |
| Current | 182A |
| Power | 20KW. |
| Output voltage tolerance | 110VDC ± 1V. |
| Ripple (mVp-p) at O/P connector | <=1% of Vnom at 20Mhz bandwidth with 1uf ceramic cap at RF probe. |
| Line Regulation | <=1% of Vnom at output connector. |
| Load Regulation | <=1% of Vnom at output connector. |
| LED Indications | Input Red & Output Green. |
| Over-Voltage Protection | Protection operative above 120-140VDC of independent output. |
| O/P protection | Over-load, Short-circuit, Over-Voltage, Over-temp protected. |
| Efficiency | >88% at full load with 230VAC input. |
| Vibration | 10 - 55Hz, 19.6m/s² (2G) |
| Impact | 196.1m/s² (20G), 11ms, Once each X, Y, & Z. |
| Agency Approvals | UL60950-1, C-UL (CSA60950-1), EN60950-1, EN50178 Complies with DEN-AN. |
| Conducted Noise | Complies with FCC-A, VCCI-A, CISPR22-A, EN55011, EN55022,,50081 |
| Harmonic Attenuator | Complies with IEC61000-3-2 class A. |
| Mounting | Movable Rack with caster (front and rear door) |
| Depth | 650mm |
| Width | 600mm |
| Height | 1743mm (36U) without caster |
| Weight (unpacked) | 100Kg Apx |
| Input | Cu Buss Bar termination |
| Output | Cu Buss Bar termination |