Home /GHA700F

| Voltage | 85–264VAC, 1 Phase (Refer to Derating and Instruction Manual 1.1) |
| Current |
ACIN 115V: 7.0A typ. ACIN 230V: 3.5A typ. |
| Frequency | 50 / 60Hz (45–66Hz) |
| Power Factor |
ACIN 115V: 0.95 typ. ACIN 230V: 0.90 typ. |
| Inrush Current |
ACIN 115V: 20A typ. ACIN 230V: 40A typ. At rated load, cold start, Ta=25°C. |
| Earth Leakage Current | 100/200µA max (ACIN 100/264V 60Hz, at rated load, according to IEC60601-1) |
| Touch Current | 100µA max (ACIN 264V 60Hz, at rated load, according to IEC60601-1) |
| Operating Temperature | -20°C to +80°C |
| Operating Humidity | 20–90% RH (Non-condensing) |
| Operating Altitude | 3,000m (10,000 feet) max |
| Storage Temperature | -30°C to +80°C |
| Storage Humidity | 20–90% RH (Non-condensing) |
| Storage Altitude | 9,000m (30,000 feet) max |
| Vibration | 10–55Hz, 19.6m/s² (2G), 3 minutes period, 60 minutes each along X, Y and Z axis. |
| Impact | 196.1m/s² (20G), 11ms, once each X, Y and Z axis. |
| Parameter | GHA700F-12 | GHA700F-24 | GHA700F-30 | GHA700F-48 | GHA700F-56 |
|---|---|---|---|---|---|
| Maximum Output Wattage (W) | 650.4 | 700.8 | 699.0 | 700.8 | 700.0 |
| Output Voltage (V) | 12 | 24 | 30 | 48 | 56 |
| Forced Air Current at 50°C (A) | 54.2 | 29.2 | 23.3 | 14.6 | 12.5 |
| Convection Current at 30°C (A) | 33.4 | 16.7 | 13.4 | 8.4 | 7.2 |
| Convection Current at 50°C (A) | 22.2 | 11.1 | 8.9 | 5.6 | 4.8 |
| Conduction Cooling Current at 50°C (A) | 33.4 | 16.7 | 13.4 | 8.4 | 7.2 |
| Line Regulation (mV) max. | 48 | 96 | 120 | 192 | 192 |
| Load Regulation (mV) max. | 100 | 150 | 180 | 240 | 240 |
| Ripple (mVp-p), 0 to +50°C | 240 | 300 | 350 | 550 | 600 |
| Ripple (mVp-p), -20°C to 0°C | 320 | 400 | 500 | 700 | 750 |
| Ripple Noise (mVp-p), 0 to +50°C | 300 | 400 | 450 | 650 | 700 |
| Ripple Noise (mVp-p), -20°C to 0°C | 360 | 500 | 600 | 800 | 850 |
| Temperature Regulation (mV), 0 to +50°C | 120 | 240 | 300 | 480 | 600 |
| Temperature Regulation (mV), -20°C to +50°C | 150 | 290 | 360 | 600 | 720 |
| Drift (mV) | 48 | 96 | 120 | 192 | 192 |
| Output Voltage Adjustment Range (V) | 11.40–13.20 | 22.80–26.40 | 28.50–33.00 | 45.60–52.80 | 53.20–61.60 |
| Output Voltage Setting (V) | 12.00–12.48 | 24.00–24.96 | 30.00–31.20 | 48.00–49.92 | 56.00–58.24 |
| Start-up Time | 500ms typ. (ACIN 115V, at rated load) |
| Hold-up Time | 12ms typ. (ACIN 115V, at rated load) |
| Input | Output Load | GHA700F-12 | GHA700F-24 | GHA700F-30 | GHA700F-48 | GHA700F-56 |
|---|---|---|---|---|---|---|
| ACIN 115V | 400W | 94.0% | 94.0% | 94.0% | 94.0% | 94.0% |
| ACIN 115V | Maximum rated output | 92.5% | 93.0% | 93.0% | 93.0% | 93.0% |
| ACIN 230V | 400W | 95.5% | 96.0% | 96.0% | 96.0% | 96.0% |
| ACIN 230V | Maximum rated output | 94.5% | 95.5% | 95.5% | 95.5% | 95.5% |
| Overcurrent Protection | Works over 105% of rating and recovers automatically. |
| Overvoltage Protection – 12V | 13.80–16.80V |
| Overvoltage Protection – 24V | 27.60–33.60V |
| Overvoltage Protection – 30V | 34.50–42.00V |
| Overvoltage Protection – 48V | 55.20–67.20V |
| Overvoltage Protection – 56V | 64.40–78.40V |
| AUX1 (12V, 1A) | Optional (Excluding GHA700F-12) |
| AUX2 (5V, 1A) | Optional |
| Remote ON/OFF | Optional |
| Power Good | Optional |
| Input–Output–RC–AUX | AC 4,000V, 1 minute, cutoff current 10mA; DC 500V, 50MΩ min. (Room Temperature), 2MOPP |
| Input–FG | AC 2,000V, 1 minute, cutoff current 10mA; DC 500V, 50MΩ min. (Room Temperature), 1MOPP |
| Output–RC–AUX–FG | AC 1,500V, 1 minute, cutoff current 10mA; DC 500V, 50MΩ min. (Room Temperature), 1MOPP |
| Output–RC–AUX | AC 500V, 1 minute, cutoff current 25mA; DC 500V, 50MΩ min. (Room Temperature) |
| Approvals | UL62368-1, ANSI/AAMI ES60601-1, C-UL (equivalent to CAN/CSA-C22.2 No.62368-1, CAN/CSA-C22.2 No.60601-1), EN62368-1, EN60601-1 3rd, Complies with IEC60601-1-2 4th Ed., EN61558-2-16 (OVC III), DEN-AN |
| Conducted Noise | Complies with FCC-B, VCCI-B, CISPR32-B, EN55011-B, EN55032-B |
| Harmonic Attenuator | Complies with IEC61000-3-2 (Class A) |
| Case Size (W × H × D) | 76.2 × 38.1 × 127mm |
| Case Size (inches) | 3 × 1.5 × 5 inches |
| Weight | 570g max. |
| Cooling Method | Convection, Forced air (Require external fan), Conduction cooling |
GH A 700 F -OO -O
| 1. | Series Name |
| 2. | Single Output |
| 3. | Output Wattage |
| 4. | Universal Input |
| 5. | Output Voltage |
| 6. | Optional Features |
| C | With Coating |
| E | IEC Class II |
| R3 | With Subfeatures (5V AUX, 12V AUX, Remote, Power Good). Excluding GHA700F-12. |
| T3 | Mounting hole M3 |
| U1 | Can attach an external capacitor unit |
EAC-16-472
High voltage pulse noise type: EAP series
Low leakage current type: EAM series
A higher current rating EMI/EMC filter may be recommended in view of the other devices that could be connected in parallel with the power supply.
This power supply is manufactured by SMD technology. The stress to P.C.B like twisting or bending causes the defect of the unit, please handle the unit with care.
Make sure necessary tests will be carried out on your end equipment with the power supply installed in accordance with any required EMC/EMI regulations.