IN-D-240-DD-S-J

Home /IN-D-240-DD-S-J

Model:IN-D-240-DD-S-J

Features
  • Natural Convection Cooling.
  • 48VDC Input / 48VDC Output.
  • Input transients & reverse polarity protection.
  • Rugged DC/DC Converter for Industrial applications.
  • Over-voltage / Short-circuit / Over-current / Over-temperature protected.
Environmental
Operating Temperature-20°C to +60°C (Derating > 75°C)
Storage Temperature-40°C to +100°C
Relative Humidity20–90% RH (Non-condensing)
CoolingConvection Cooling
Design Conformance
Vibration10 - 55Hz, 19.8m/s² (2G)
Safety StandardsUL60950-1 (Design Conformance)
Switching Frequency370 KHz
Input Specifications
Input Voltage48VDC (Range: 36V - 76V)
Input Current8.5A at Nominal 48VDC
Inrush Current<15A typical
Switch-On Delay<100ms
Isolation Input-Case: 500VDC, 30MΩ
Input-Output: 500VDC, 30MΩ
Output-Case: 500VDC, 30MΩ
Input ProtectionReverse Polarity and Over Current via Input Fuse
Output Specifications
Output Voltage48VDC (±1% Tolerance)
Output Current5.0A
Output Power240W
Ripple (mVp-p)150 max. (20 MHz bandwidth)
Ripple Noise120 max.
Line Regulation≤1% of Vnom
Load Regulation≤1% of Vnom (Exclusive OR-ing drop max 0.5VDC)
Output Voltage Adjustment22 to 26VDC
Output Protection Over-load, Short-circuit with Power Limitation
Auto Recovery after Fault Removal
OR-ing DiodeInbuilt for Output Redundancy and Power Sharing
Relay ContactC, NO: Short for OK, Open for Fault
Efficiency>87% (10% to 100% Load, excluding OR-ing & Reverse Polarity losses)
LED Indications DC Input (Green)
DC OK (Green)
DC Low / Fault (Red)
Mechanical
MountingBack Plane / DIN Rail
EnclosureCabinet IP42
Depth144mm
Width70mm
Height130mm
Weight (Unpacked)<1.2Kg Approx.
Connectors
TypeScrew Terminals